Round Zone Dampers
Jackson Systems
The "D" series dampers are galvanized steel, single blade dampers complete with a 24 Volt, spring return actuator. These dampers are shipped complete and ready for installation. The "D" series damper can be installed in any position in any properly sized duct. They are rated for duct systems less than 1.0" W.C.
Dampers are available in 5", 6", 7", 8", 9", 10", 12", 14", 16", and 18" diameters. Dampers are ordered as D-xx, where xx is the 2-digit diameter.
"D" series dampers are typically shipped as normally open dampers that are powered closed and spring return open. A unique feature is that they can be easily field converted from powered closed to powered open.
The "D" series damper is powered by a 24 Volt AC, 50/60 Hz, spring return damper motor. The motor powers the damper closed and spring returns the damper open for fail-safe operation. Providing power to the motor drives the damper closed. Removing power from the motor allows it to spring back to the open position.
The 24 Volt, synchronous motor has been tested over 250,000 cycles to provide long life. To replace the motor, simply loosen the setscrew holding the motor to the damper.
The "D" series damper has a simple adjustment for setting the minimum position. Minimum position allows for bypass air. To set minimum position, loosen the setscrew, align the setscrew to the minimum position label and re-tighten."