The Cleveland Controls AFS-298-112-148 is a precision-engineered air pressure sensing switch designed for reliable performance in HVAC, combustion, and air-handling applications. Built to handle both air and combustion by-products that will not degrade silicone, this switch is a dependable solution for systems requiring accurate differential pressure monitoring and automatic contact switching.

How It Works

The AFS-298-112-148 monitors system air pressure and changes its electrical contacts on increasing pressure. When pressure rises to the set point of 0.45″ w.c. (± 0.05″ w.c.), the switch actuates, making it ideal for proving airflow, monitoring fan operation, filter status, or burner draft conditions in residential and commercial HVAC equipment.

Key Specifications
  • Sensing Range: 0.05″ w.c. ± 0.02″ w.c. to 12″ w.c.
  • Set Point: Change contacts on increasing pressure at 0.45″ w.c. ± 0.05″ w.c.
  • Supply Voltage: 120V–277Vac
  • Maximum Inlet Pressure: ½ PSI (0.5 PSI)
  • Compatible Media: Air or combustion by-products that will not degrade silicone
  • SKU: AFS-298-112-148
Features & Benefits
  • Wide voltage compatibility (120V–277Vac) for flexible installation across commercial and industrial systems
  • Accurate set-point actuation ensures reliable airflow and pressure proving
  • Silicone-compatible media rating supports use in combustion and flue gas environments
  • Broad sensing range (0.05″ to 12″ w.c.) accommodates a variety of HVAC pressure monitoring applications
  • Compact, purpose-built design from Cleveland Controls — a trusted name in air pressure sensing
Typical Applications
  • Airflow proving in furnaces, air handlers, and rooftop units
  • Draft inducer and combustion blower monitoring
  • Filter status and dirty filter detection
  • Fan failure detection and interlock control
  • Commercial HVAC pressure monitoring and safety shutdown circuits

Additional information

Voltage

120V – 277V AC

Sensing Range

0.05" w.c. – 12" w.c.

Set Point

0.45" w.c. ± 0.05" w.c.

Inlet Pressure Max

0.5 PSI

Switch Action

Increasing Pressure

Compatible Fluid / Media

Air, Combustion By-Products (Silicone-Compatible)

Application

Airflow Proving, Combustion Blower Monitoring, Draft Inducer Monitoring, Fan Failure Detection, Filter Status Detection, HVAC Pressure Monitoring