Description

The Copeland 099008 is a PS2 Series Dual Pressure Control engineered for precise refrigeration and HVAC system protection. Combining both low-pressure and high-pressure monitoring in a single, robust control, it safeguards compressors and system components against unsafe operating conditions — helping prevent costly equipment damage and downtime.

The low-pressure side features a wide adjustable setpoint range with automatic reset, allowing the system to resume normal operation once safe pressures are restored. The high-pressure side provides a broad setpoint range with a fixed differential and manual reset, ensuring a technician must verify conditions before the system restarts after a high-pressure trip — a critical safety feature for protecting compressors and refrigerant circuits.

Low Pressure Specifications
  • Low Pressure Setpoint Range: 9″Hg to 102 psig
  • Low Pressure Differential Setpoint Range: 15 to 73 psig
  • Low Pressure Reset: Automatic
High Pressure Specifications
  • High Pressure Setpoint Range: 87 to 464 psig
  • High Pressure Differential: Fixed
  • High Pressure Reset: Manual
Key Features
  • Dual pressure control — monitors both low and high side in one unit
  • Wide low-pressure setpoint range from deep vacuum (9″Hg) to 102 psig
  • High-pressure setpoint range up to 464 psig for high-side protection
  • Automatic low-pressure reset for unattended system recovery
  • Manual high-pressure reset for added safety and technician oversight
  • Fixed high-pressure differential for consistent, repeatable cutout performance
  • PS2 Series design built for reliable field performance
Typical Applications
  • Commercial refrigeration systems
  • Air conditioning and heat pump equipment
  • Compressor protection on split and packaged systems
  • Low-ambient and high-ambient pressure safety control

Additional information

Low Pressure Setpoint Range

9" Hg – 102 PSI

Low Pressure Differential Setpoint Range

15 PSI – 73 PSI

Low Pressure Reset

Automatic

High Pressure Setpoint Range

87 PSI – 464 PSI

High Pressure Differential

Fixed

High Pressure Reset

Manual

Application

Air Conditioning, Commercial Refrigeration, Compressor Protection, Heat Pump