Overview

The Honeywell V4943B1019 is a single-stage pressure regulating valve engineered for reliable natural gas flow control in commercial and industrial HVAC applications. Featuring a 1″ pipe connection and 120VAC operation, this valve delivers precise pressure regulation with a factory-set output of 3.5″ water column, making it ready for immediate installation with minimal field adjustment.

Key Features
  • Single-stage pressure regulating valve design for consistent downstream gas pressure
  • 1″ pipe connection for straightforward integration into standard gas train assemblies
  • 120VAC operating voltage for compatibility with common commercial control circuits
  • Natural gas service — optimized for NG fuel systems
  • High fire regulator setpoints adjustable from 3″ to 4.5″ water column
  • Factory-set outlet pressure of 3.5″ water column for out-of-the-box convenience
  • Flow capacity range of 300–1,000 CFH to accommodate a wide variety of burner applications
  • Valve opening time of 3–25 seconds (field adjustable) for controlled, safe light-off sequences
  • Maximum valve closing time of 2 seconds for fast, reliable shutoff
Specifications
  • SKU: V4943B1019
  • Brand: Honeywell
  • Valve Type: Single Stage Pressure Regulating
  • Pipe Size: 1″
  • Voltage: 120VAC
  • Gas Type: Natural Gas
  • High Fire Regulator Setpoints: 3″ – 4.5″ Water Column
  • Factory Outlet Pressure Setting: 3.5″ Water Column
  • Flow Capacity: 300 – 1,000 CFH
  • Valve Opening Time: 3 – 25 Seconds
  • Maximum Valve Closing Time: 2 Seconds
Applications

Ideal for use in commercial boilers, industrial burners, rooftop units, and other gas-fired HVAC equipment requiring precise pressure regulation and controlled valve sequencing. The adjustable opening time allows technicians to fine-tune the light-off sequence for optimal combustion safety and efficiency.