Description
Honeywell V8944B1035 Two Stage Pressure Regulating Gas Valve Overview
The Honeywell V8944B1035 is a two-stage pressure regulating gas valve engineered for reliable, precise control of natural gas in commercial and residential heating applications. With a 1-1/2″ pipe connection and 24VAC control voltage, this valve delivers accurate two-stage gas flow regulation to optimize burner performance, improve combustion efficiency, and reduce fuel consumption.
Two-Stage Regulation for Optimized Combustion
Designed for two-stage burner systems, the V8944B1035 independently regulates high-fire and low-fire outlet pressures. The high-fire regulator is field-adjustable between 3″ and 4.5″ water column (W.C.), with a factory setting of 3.5″ W.C. The low-fire regulator is adjustable between 0.8″ and 2″ W.C., with a factory setting of 0.8″ W.C. This dual-stage control allows the burner to operate at a reduced capacity during low-demand periods, maximizing efficiency and extending equipment life.
Key Specifications
- SKU / Model: V8944B1035
- Pipe Size: 1-1/2″
- Control Voltage: 24VAC
- Gas Type: Natural Gas
- High Fire Regulator Setpoint Range: 3″ – 4.5″ Water Column
- High Fire Factory Setting: 3.5″ Water Column
- Low Fire Regulator Setpoint Range: 0.8″ – 2″ Water Column
- Low Fire Factory Setting: 0.8″ Water Column
- Valve Stages: Two-Stage
Features & Benefits
- Two-stage pressure regulation for precise high-fire and low-fire control
- Field-adjustable outlet pressure setpoints on both stages
- Factory pre-set for quick installation and commissioning
- 24VAC operation compatible with standard HVAC control systems
- 1-1/2″ pipe connection for straightforward integration into existing gas trains
- Designed for natural gas service
- Durable construction for long-term reliability in demanding heating environments
Typical Applications
- Commercial and industrial gas-fired heating equipment
- Two-stage burner systems requiring independent high-fire and low-fire pressure control
- Boilers, furnaces, and unit heaters using natural gas
- OEM and replacement installations requiring a 1-1/2″ two-stage gas valve







Reviews