Description
The Warrick-Gems Sensors & Controls 26MC1A0 is a plug-in liquid level control module engineered for reliable low water cutoff and liquid level detection in boiler and hydronic system applications. Its direct acting mode of operation provides straightforward, dependable response to changing liquid levels, making it a trusted solution for protecting heating equipment from low-water conditions.
Key Features
- 26,000 ohm sensing resistance for precise liquid level detection
- Direct acting mode of operation for immediate, reliable response
- 120Vac supply voltage for compatibility with standard commercial and residential electrical systems
- SPDT relay output — includes 1 Normally Open (NO) and 1 Normally Closed (NC) contact with powered contacts for versatile circuit control
- 11 Pin Octal Socket style for easy plug-in installation and field replacement
- Low water cutoff functionality protects boilers and hydronic systems from dangerous dry-fire conditions
- Plug-in module design simplifies maintenance and reduces downtime
Specifications
- SKU: 26MC1A0
- Brand: Warrick-Gems Sensors & Controls
- Sensing Resistance: 26,000 ohm
- Mode of Operation: Direct Acting
- Supply Voltage: 120Vac
- Relay Type: SPDT (1 Normally Open / 1 Normally Closed)
- Contact Type: Powered Contacts
- Socket Style: 11 Pin Octal
- Control Type: Low Water Cutoff, Plug-in Module
Application
The 26MC1A0 is ideal for use in boiler rooms, steam systems, and hydronic heating applications where low water cutoff protection is required. The plug-in octal socket design allows for fast, tool-free module swaps during service calls, minimizing system downtime. The SPDT relay with powered contacts provides flexible integration into both safety shutdown and alarm circuits.