Description
The Honeywell RP7517B1024 Electronic Pneumatic Transducer is engineered to convert a 2–10 VDC input signal into a proportional pneumatic output of 3–15 psi. Designed for direct-acting applications, this transducer ensures precise control in HVAC and industrial systems.
Features:
- Screw mounting or snap rail (models with cover).
- Factory calibrated.
- Dual barb fittings.
- High accuracy.
Specifications:
- Application: Electric to pneumatic Transducer
- Maximum Safe Operating Pressure (psi): 30 psi
- Output Pressure Range: 3 to 15 psi
- Connections: Dual barb-fittings for 1/4 in. or 5/32 in. O.D. plastic tubing
- Electrical Connections: 30 in. (762 mm) lead wire
- Action: Direct Acting
- Airflow Usage: 0.025 scfm (117mL/s)
- Max. Operating Temperature: 131 F
- Input Signal: 2 to 10 Vdc at 0.1 mA max
- Normal High End Pressure: 16 psi with 18 psi main pressure at 12 Vdc or 16 psi at 11 Vdc ( min. )
- Normal Low End Pressure: 0.5 psi at 0 Vdc
- Pressure Range: 0 to 18 psi
- Voltage: 24 Vac external transformer
- Humidity Range: 5 to 95% RH
- Comments: Without cover, external transformer required, 24 Vac, 50/60 Hz, (3 wire)