FREE STANDARD SHIPPING ON ORDERS $99+

Jackson Systems

Johnson Controls A421ABC-02C Digital Temperature Controller

BRAND: Johnson Controls SKU: A421ABC-02C

(2 customer reviews)

$108.65

120/240VAC SPDT Single-Stage Digital Temperature Controller

Free Shipping
Ships Today
Availability:

354 In Stock

Description

The Johnson Controls A421ABC-02C (replaces the older Penn A421 temperature controls) is a single-stage electronic temperature controller with an SPDT relay that switches heating or cooling loads directly at 120 V or 240 V—no auxiliary contactor required. A bright back-lit LCD and three-button keypad make temperature, delay, and setback settings easy, while an adjustable anti-short-cycle timer helps prevent compressor hard starts and trips.

 

Key Features

Wide control range

Adjusts temperatures anywhere from -40 °F to 212 °F (-40 °C to 100 °C), covering most HVAC and industrial needs.

Works on 120 V or 240 V

Direct line-voltage switching (SPDT relay) simplifies wiring for fans, pumps, heaters, or chillers.

Clear back-lit LCD

Large numbers and system icons are easy to read; brightness can be dimmed for dark mechanical rooms.

Easy On/Off set-points

Set heating or cooling cut-in and cut-out temperatures right from the keypad—no jumpers to move.

Anti-short-cycle delay

Adjustable time delay keeps compressors off for a few minutes after they stop, extending equipment life.

Temperature setback

A dry-contact input lets you shift both set-points by a chosen offset—for example, to save energy at night.

High/low limits & display offset

Lock the adjustment range for end users and fine-tune the displayed temperature to match a reference sensor.

Status LED

A front-panel light shows when the relay is energized, so you can confirm operation at a glance.

Durable enclosure

Type 1 (NEMA) / IP20 plastic housing mounts on DIN rail or directly to a flat surface; sensor with 6 ft 7 in. (2 m) lead is included.

 

Typical Uses

  • Switching boilers, chillers, or circulation pumps
  • Alarm or shutdown control when a process temperature drifts out of range
  • Fan or damper operation based on duct or water temperature
  • Cooling-tower fan cycling
  • General heating or cooling control in greenhouses, walk-in boxes, or equipment cabinets

 

Key Specifications

Power / relay rating

120 / 240 VAC line voltage, single-pole double-throw (SPDT)

Sensor supplied

A99BB-200C, 10 kΩ NTC, 6 ft 7 in. (2 m) cable

Adjustment range

-40 °F to 212 °F (-40 °C to 100 °C)

Differential (hysteresis)

Adjustable

Anti-short-cycle delay

Adjustable

Enclosure Mounting

Type 1 (NEMA), IP20, high-impact plastic

Mounting

Surface mount or 35 mm DIN rail

 

How the A421 Series works 

The A421 Series is essentially a smart, line-voltage thermostat built for equipment control duties. An external A99 sensor monitors temperature; when the reading crosses the “On” or “Off” set-points you program on the keypad, the onboard SPDT relay flips—energizing or de-energizing fans, heaters, pumps or condensing units at either 120 V or 240 V. Because the relay is rated for 1 HP, you can land the load leads directly on the controller instead of adding a separate contactor.

The A421 is adjustable for anything you come across in the field: cut-in and cut-out temperatures (-40 °F to 212 °F), a programmable temperature differential so you can tighten or widen the control band, an anti-short-cycle delay to spare compressors, and a dry-contact “setback” input for night-set or defrost cycles. You can also lock the keypad to keep from bumping set-points.

 

FAQs

What is the differential range on an A421ABC-02C?

The temperature differential—the span between turn-on and turn-off—is adjustable from 1 °F to 30 °F

 

Setup Instructions

  • Access Setup Mode:
    • Navigate the three-button interface via Menu, Up, Down to access Basic and Advanced menus.
  • Set Temperature Differential:
    • Under Basic menu, set OFF (cut-out temp) and ON (cut-in temp). The differential (Diff = OFF – ON) can be anywhere between 1 and 30 °F.
  • Adjust Anti‑Short‑Cycle Delay (ASd):
    • In Basic or Advanced menus, configure ASd (anti-short cycle delay) from 0 to 12 minutes to prevent compressor or heater short cycling.
  • Enable Temperature Setback (tSb):
    • In Advanced settings, you can program a setback offset (–50 to +50 °F). To activate it, wire a dry contact to the BIN input and enable setback via the parameter setting.

Additional information

Enclosure

NEMA-1

Lead Wire Length

6.5 ft

Temperature

-40°F (-40°C) Min, 212°F (100°C) Max

Installation Instructions

Product Overview

You may also like…

Are you a contractor? Join TradesElite Today!