FREE STANDARD SHIPPING ON ORDERS $99+

Jackson Systems
Menu

York S1-024-34561-000 .95/.4″WC Dual Pressure Switch

BRAND: York SKU: S1-024-34561-000

$117.96

MSRP: $135.65
You save 15%

.95/.4″ WC Dual Pressure Switch, OEM Replacement Part

Free Shipping
Ships Next Business Day
Availability:

13 In Stock

Description

The York S1-024-34561-000 is an OEM replacement dual pressure switch designed for use in York gas furnaces and air handlers. Calibrated to precise setpoints of .95″ WC (close) and .4″ WC (open), this pressure switch monitors the negative pressure generated by the inducer motor to verify proper draft and venting conditions before allowing the ignition sequence to proceed — a critical safety function in any induced-draft or condensing furnace application.

How It Works

The pressure switch senses the pressure differential created by the draft inducer blower. If the inducer fails to establish adequate airflow, the switch remains open, preventing the gas valve from energizing and protecting against unsafe combustion conditions. Dual setpoints allow the switch to monitor both stages of operation with accuracy.

Key Features
  • OEM York replacement part — direct fit for compatible York furnace models
  • Dual pressure setpoints: .95″ WC (close) / .4″ WC (open)
  • Monitors inducer draft pressure for safe ignition sequencing
  • Prevents gas valve operation under inadequate draft conditions
  • Reliable diaphragm-style pressure sensing mechanism
  • Designed for induced-draft and condensing furnace applications
Application
  • Compatible with select York gas furnaces — verify model compatibility before ordering
  • Replaces worn, failed, or out-of-calibration pressure switches
  • Suitable for residential and light commercial HVAC systems
Why Replace Your Pressure Switch?

A faulty pressure switch is one of the most common causes of furnace no-heat calls. Symptoms include the inducer running but the furnace failing to light, error codes related to pressure switch faults, or nuisance lockouts. Replacing with the correct OEM part ensures proper calibration and reliable performance season after season.

Additional information

Sensor Type

Diaphragm

OEM / Aftermarket

Yes

Application

Air Handlers, Condensing Furnaces, Gas Furnaces, Induced-Draft Furnaces, Light Commercial HVAC, Residential HVAC

Measured Parameter

Draft Pressure

Reviews

There are no reviews yet.

Be the first to review “York S1-024-34561-000 .95/.4″WC Dual Pressure Switch”

Your email address will not be published. Required fields are marked *

Are you a contractor? Join TradesElite Today!